|
Procedures For
The Design, Analysis And Auditing
Of Static Control Flooring/Footwear Systems
Stephen L. Fowler
Fowler Associates, 3551 Moore-Duncan Hwy, Moore, SC 29369
Tel: 864-574-6415, FAX: 864-576-4992, Email:
sfowler@sfowler.com
William G. Klein
K&S Laboratories, 2026 Bay Rd., Stoughton, MA 02072
Tel: 617-341-8331, FAX: 617-341-8331, Email: kslabs@thecia.net
Larry Fromm
Hewlett Packard, 1501 Page Mill Rd., Palo Alto, CA 94304
Abstract - It is the purpose
of this paper to show that the electrostatic performance of footwear/flooring
systems, defined as the electrostatic potential of personnel arising
out of the use of these systems, can be predicted with adequate
precision based on component resistance data alone, and further
to present resistance testing methodologies which are at once more
relevant and more reproducible than most in common usage today.
Conclusions, which are to a considerable extent a matter of opinion
though based on hard data, suggest that inappropriately defined
criteria and overly stringent specification are significant problems
today to users, suppliers, and auditors.
Background and Introduction
It is generally accepted that the
resistance and triboelectric properties of footwear and flooring
materials together constitute the main parts of the system which
limit the electrostatic body voltage of a person walking on the
floor. Charge decay time may also be inferred from resistance data.
Unfortunately, the use of resistance to predict or define quantitatively
the electrostatic performance of flooring/footwear systems has been
fraught with many problems. The problems are not trivial because
the industry-wide failure to establish appropriate standards for
the measurement of components and the performance of systems and
the consequent use of various methodologies yielding significantly
different values have often led to serious difficulties. These difficulties
have resulted, for example, in both failed installations and expensive
claims of failure not based on "true" criteria of performance.
It is not possible to set up universally useful standardized criteria
for product design, field performance, or auditing procedures without
a significant degree of basic knowledge and an agreement within
the ESD community as to the specific, quantifiable objectives toward
which these criteria are aimed. With different manufacturers and
different users playing by different rules, chaos has resulted.
Past work (2,3) has addressed
some of the difficulties and has suggested solutions in defining
relevant criteria for the design and evaluation of static controlled
flooring, footwear, and flooring/footwear systems. It has not, however,
had any noticeable effect on the way that floors and shoes are specified
and tested, nor has there been any systematic effort to reconcile
the troublesome differences. It is well understood that the rule
of thumb for personnel voltages of a hard grounded worker are as
follows: at 100 Meg W the personnel voltages may be over 100 Volts
; at 10 Meg W personnel voltages will usually be less than 100 Volts;
at 1 Meg W the expected personnel voltages are in the 10 Volt range.
Flooring and footwear systems are more complex than a simple wriststrap
grounded situation. The current work expands on past work, introduces
new methodologies which are both reproducible and relevant, and
verifies the assertions made with quantitative data from both the
laboratory and operative factory installations. A critical examination
will be made as to how some currently used test methodologies fit
into this picture, specifically ESD 7.1, ASTM F-150, NFPA 99, ESD
9.1 and IEC 1340-4-1. It is hoped that this work will be sufficiently
intriguing to lead to a concerted effort to develop and promulgate
a performance oriented set of specifications and more universally
accepted evaluation and auditing procedures.
This work is aimed equally at those
whose good fortune it is to have the freedom to write specifications
for new installations and those tortured souls who must make critical
choices and compromises in the utilization, modification, or scrapping
of existing non-conforming flooring
Basic System Analysis
In order to intelligently approach
the issue of specifying and evaluating the resistance properties
of footwear and flooring as they affect body voltages, it is necessary
to have some reasonable idea as to how these properties act and
interact together with other pertinent system parameters. This is
a highly complex problem for which there is no easy solution. Briefly,
some common deficiencies of often cited analyses consist of:
-
the concept of linear, lumped
parameters when they are in fact neither linear nor lumped;
-
neglect or inadequate definition
of important variables; and
-
the use of a steady state approach
to a dynamic event.
The list could go on. An example
of this sort of specious reasoning is the popular representation
of the human walker as a parallel plate capacitor with constant
charge. Although it is tempting to use such a configuration, which
sort of looks like a foot on the floor and is simple electrically,
it suffers from all three deficiencies mentioned above and has virtually
no analytical value. It is well beyond both the scope and purpose
of this paper to delve deeply into this issue. Rather, we shall
simply attempt to put the problem into a proper perspective so that
the simplifications used to deal with the area of very low personnel
static will be both credible and useful.
Figure 1: Equivalent Circuit
Figure
(1) shows a highly simplified "equivalent" circuit7
of a person walking on a floor surface. It is presented here not
as a model from which to make calculations, but as a demonstration
tool to indicate the complexity of the general problem and as a
basis for useful further simplification in the special case of interest
here, a high degree of static control resulting in very low body
voltages. The static potential on the individual is the result of
the interfacial EMF’s due to triboelectrification, the surface neutralization
at the foot/floor interface where the foot is down, and the flow
of current through the same interface in response to a body potential
to ground. While it is conventional to consider this flow, and therefore
the body resistance to ground, to be the main controlling factor
in limiting body voltage this is strictly true only for body charges
originating from sources other than the shoe and floor. In order
to segregate the effects of dissipation to ground and minimization
of surface accumulation of charge, body voltages under dynamic conditions
were measured with the various flooring/footwear combinations in
a normal manner and also with the body insulated from ground by
nonconductive shoe inserts. Maximum body voltages will be quantitatively
characterized by shoe sole resistance, floor surface resistance,
and body to ground resistance. It will be shown that, for the resistance
levels used in static controlled systems, the surface resistances
of the sole and floor are the main controlling factors.
Since our interest here is more
than academic, it will be necessary to define and justify our test
methodologies for both body voltage and resistances.
Test Methodologies
A. Measurement of Body Potential
Since body potential is taken in
this work to be the criterion of electrostatic performance in a
floor/shoe system, it is imperative that there be an understanding
of the way that it is generated, measured, and reported. First,
the measuring equipment must possess certain basic properties. It
must not constitute in itself a significant electrical part of the
body/footwear/floor system and its frequency response must be sufficient
to capture the voltage pattern without distortion. Both of these
conditions were satisfied by the equipment used in this work. It
is of interest to note here that some test runs were performed with
bandwidths of both 5Hz and 100KHz with no discernible difference
in peak value readings. Peak values were determined in two ways,
from a new versatile peak hold LED array instrument and by observation
of an oscilloscope trace. For the body of the work, a 100KHz bandwidth
was used.
The
manner in which the test voltage is generated is important. Figure
2 is a sketch of the means.
A person holding a probe walks on
a test surface wearing test shoes and his peak voltage is recorded.
This procedure has been rather generally used for a large number
of years. Except for the peak voltage criterion, it is the same
as that required by AATCC TM-13412, which calls for a
damped response, and it is substantially the same as a Work in Process
standard of the ESD Association. Basically, both say the same thing:
if you want to find out what happens when you walk on a floor, walk
on it and see.
Figure 2: Body Voltage Test
Method
The differences among various methodologies
presented in the literature reside in the prescribed method of walking
for test purposes. While this is not usually a significant factor,
it can be. In this work we have adopted a brisk natural gait for
tests made in the field and a brisk, short, slightly high step for
laboratory work where one can hardly walk naturally on a three or
four foot square test specimen. This lab step produces, as observed
on an oscilloscope, the highest voltages short of doing anything
really wild.
These procedures clearly exaggerate
the danger of any real human body discharge, at least statistically,
as they involve high generation motions and define peak values of
very short duration which, in any likely real life situation, would
not be seen by a sensitive device.
B. Shoe Resistances
Three
types of resistance measurement have been used to characterize the
resistance properties of shoes. The ESD Association has a method
S9.18 which involves lining a shoe with foil, loading
it with metal shot, and measuring the resistance to a base plate
from the foil. We have found that this method does not adequately
represent the body resistance from shoe to ground in normal wear.
We have not used that method in this work. Previous work (2,3)
has demonstrated the measurement of body resistance to ground using
an actual body. This is also the general methodology of the ANSI
Z-419 standard and is one type of evaluation we use here.
The third method is one we also use - the measurement of shoe sole
surface resistance. This has been described in other work (3)
but has been slightly modified by the use of a convenient
step-on floor test unit which gives rapid, reproducible results
and is suitable for on site testing. It may also be hand held as
shown. This procedure is diagrammed in Figure 3.
Figure 3: Sole Surface Resistance Measurement
C. The Measurement of Flooring
Resistance
It
is critical that the measurement of the resistance of flooring be
capable of producing reproducible results anywhere, any time, and
by anyone, assuming samples of reasonably similar properties as
this is a main criterion in virtually all specifications and audits.
Today this is far from the case with the use of different methodologies
as well as considerable variations even when nominally using the
same method. As will be shown later, considerable variations in
resistance properties may not be of great functional significance,
but specifications must be made and standards must be met. Too often
a material hovers between acceptance and rejection based on who
makes the test and when. Four methods are in common use today, NFPA
99, ASTM F-150, ESD 7.1 and IEC 1340-4-1. 6,10,11 All
are quite similar and are based on NFPA 99, using identical 2 ½
inch, 5 pound electrodes (except for the IEC method which uses a
2 inch, 5 kg electrode). Aside from the differences in specified
voltages and environmental conditions (100 or 500 volts, 12 or 50%
RH), which could easily be reconciled by discussion, their fundamental
flaw is the electrodes. They simply do not simulate the feet. The
light weight and relatively hard surface of the NFPA electrodes
render the resistance readings significantly sensitive to surface
unevenness and even minor surface contamination. Much higher variability
accompanies the use of a 100 volt test potential as in ESD 7.1,
although this does seem like a reasonable level considering the
intended purpose. Our test results from the lab and in the field
indicate that more relevant and more reproducible results can be
obtained by the use of heel electrodes rather than the 5 pound weights.
The type of heel electrode used, which is now commercially available,
is shown in Figure 4.
The area of the conductive contact
is the same as that of the conventional electrodes and is made from
heel grounder material. The pressure of the contact from body weight
and the relative softness of the electrode both tend to produce
a good electrical contact, just as a heel grounder or ESD shoe sole
would do. Another advantage of this method is the great speed with
which readings can be taken, thus encouraging large samplings which
can be legitimately quantified statistically. Another important
advantage is the virtual elimination of bias in floor resistance
testing. Most auditors will, when they find a bad spot, wiggle the
electrode a little or move it to an adjacent spot to try to get
a good reading. This is probably legitimate from a functional point
of view, but does leave too much room for personal judgment. It
should be noted that, as described in previous work (2),
significant surface homogeneity of resistance demands a modified
electrode material for proper evaluation.
Figure 5 shows the surface to ground
readings on a vinyl tile panel where 21 marked points were tested
by the methodologies of ESD 7.1 and with heel electrodes, both at
100 volts.

Figure 5: Heel Electrode vs. S7.1
Electrode
The difference is obvious. It is
not clear how much this difference would matter functionally, but
it would certainly be important if you had a 1 or 2 Megohm specification
to meet.
Figures 6 and 7 show comparative results
on a much less conductive vinyl using both 100 and 500 volts with
the ESD/NFPA electrodes and both surface-to-surface and surface-to-ground
configurations.
It can be stated that in general
that the heel electrode methodology using 100 Volts yields resistance
readings which are lower and less variable than S7.1 type tests
at 100 Volts. On average, the values obtained at 100 Volts using
the heel electrodes tend towards those of the 500 Volt, 5 lb. electrode
tests, but with less variability.

Figure 6: Heel Electrode vs. S7.1
Electrode

Figure 7: Heel Electrodes vs.
S7.1 Electrodes
Figure 8 shows the ordered values
for an audit-type run at a major electronic manufacturing facility.

Figure 8: Audit Data -- Surface-to-Ground
It contains approximately 285 observations
made on a vinyl tiled floor. It is worthy of note for two reasons.
First, because it contains so much more data than is usually amassed
in a single area audit, a valid statistical analysis is possible;
and second, because it takes one man with meter and computer in
hand only about 30 minutes to do this job.
It should also be noted here that
this installation outright failed the user’s specification for resistance
and yet, with proper footwear easily met the performance requirement
of body potentials below 100 volts. The quantitative explanation
for this is to be found in the experimental work reported in the
next section.
Body Voltage Test Results
The following data was generated in
two ways. First there is laboratory work under controlled conditions
and with limited sample size and second, in the field under normal
working conditions. Figure 9 summarizes the laboratory data.
|
|
|
|
Voltage Generated (Volts)
|
|
|
|
|
Floor Coverings
|
|
|
|
|
|
Conductive Flooring
|
|
|
|
Shoe Sole
|
Footwear Resistance (Ohms)
|
Aluminum
Plate
|
Vinyl#1F
|
Vinyl#2F
|
Carpet
|
PVC#1M
|
Lab Floor
Nylon
|
Control
Nylon
|
|
|
Sole
|
To Gnd
|
Feet Insulated From Shoes
|
|
Neolite
|
1.0E12
|
> 3.0E11
|
2500
|
3500
|
4000
|
600
|
600
|
2000
|
7500
|
|
Plain PU
|
3.0E10
|
> 3.0E11
|
130
|
1300
|
1500
|
800
|
70
|
680
|
2100
|
|
SD PU
|
9.0E8
|
> 3.0E11
|
20
|
220
|
240
|
40
|
20
|
390
|
3200
|
|
S6699
|
5.0E7
|
> 3.0E11
|
2
|
60
|
80
|
20
|
30
|
50
|
2400
|
|
Rubber #2
|
1.6E5
|
> 3.0E11
|
20
|
170
|
300
|
90
|
55
|
210
|
7000
|
|
O.R.
|
1.4E5
|
> 3.0E11
|
55
|
100
|
150
|
60
|
15
|
150
|
2400
|
|
|
|
|
Shoes Worn In Normal
Manner
|
|
Neolite
|
1.0E12
|
3.0E11
|
2500
|
3500
|
4500
|
600
|
400
|
2000
|
7500
|
|
Plain PU
|
3.0E10
|
8.0E9
|
130
|
1000
|
1100
|
700
|
60
|
420
|
2000
|
|
SD PU
|
9.0E08
|
5.0E7
|
13
|
75
|
80
|
40
|
15
|
340
|
2500
|
|
S6699
|
5.0E07
|
2.0E6
|
1
|
20
|
30
|
5
|
30
|
50
|
2000
|
|
Rubber #2
|
1.6E05
|
6.0E5
|
1
|
50
|
80
|
30
|
15
|
175
|
6500
|
|
O.R.
|
1.4E05
|
4.0E5
|
1
|
20
|
20
|
5
|
15
|
120
|
2000
|
|
Floor Covering Surface Resistance (Ohms)
|
1
|
5.0E5
|
1.0E7
|
3.0E7
|
7.0E9
|
4.0E10
|
1.0E12
|
Figure 9: Flooring/Footwear Body
Voltage Test Data
It shows peak voltages on a test
individual with footwear and floor resistances defined and measured
as described above under two different body /shoe relationships,
normal wear and with both feet insulated from the shoes by means
of high resistance polyethylene booties.
Figure 10 is a chart giving the
conversion of resistance data from engineering notation to logarithms.
|
Shoe
|
Resistance - W
|
Log R
|
Resistance - W
|
Log R
|
|
|
Sole
|
Sole
|
To Ground
|
To Ground
|
|
Neolite
|
1.0E12
|
12.00
|
3.0E11
|
11.48
|
|
Plain PU
|
3.0E10
|
10.48
|
8.0E9
|
9.90
|
|
SD PU
|
9.0E8
|
8.95
|
5.0E7
|
7.70
|
|
S6699
|
5.0E7
|
7.70
|
2.0E6
|
6.30
|
|
Rubber #2
|
1.6E5
|
5.20
|
6.0E5
|
5.78
|
|
O.R.
|
1.4E5
|
5.14
|
4.0E5
|
5.60
|
|
Floor Covering
|
Resistance
|
Log R
|
|
Aluminum Plate
|
1
|
0.00
|
|
Vinyl #1F
|
5.0E5
|
5.70
|
|
Vinyl #2F
|
1.0E7
|
7.00
|
|
Carpet
|
3.0E7
|
7.48
|
|
PVC #1M
|
7.0E9
|
9.85
|
|
Lab Floor-Nylon
|
4.0E10
|
10.60
|
|
Nylon Control
|
1.0E12
|
12.00
|
Figure 10: Resistance Conversion
to Log R
We prefer the logarithmic form because
it is a continuum which is easier for most people to grasp intuitively
than powers of ten with multipliers. We further believe that it
is preferable to avoid the use of such terms as "static dissipative"
and "conductive" to define quantitative ranges. It would
certainly be wrong to consider the nylon carpet in the laboratory
to be static dissipative in the same sense as more conductive flooring,
and a similar statement can be made about the plain polyurethane
shoe soles, although also nominally in the SD category. The term
"static dissipative" should be reserved for qualitative
assessments.
Figure 11 shows quite impressively
that the static development on the individual is strongly controlled
by the combination of shoe sole surface resistance and floor surface
resistance, as the body was effectively insulated from the floor
and from ground for all of these tests (>1011 Ohms).

Figure 11: Feet Insulated From
Shoes
The control resides in mutual conductivity
at the shoe/floor interface. This contention is reinforced by Figures
12a and 12b which for clarity have an expanded scale and the high
resistance has been removed. In this case there is a significant
conductive path from the body through the shoes.

Figure 12a: Shoes Worn In A
Normal Manner

Figure 12b: Shoes Worn In A
Normal Manner (detail)
Although the voltages are lower,
they are not much lower. This brings into question the wisdom of
characterizing shoe resistance by body to ground resistance alone,
as is usual, when a major part of the shoe/floor control resides
in the shoe/floor interface without regard to body-to-ground resistance.
Body-to-ground resistance is a fairly good indicator of static performance
in most cases but this is due to the usual correlation between sole
surface resistance and resistance through the shoe. (See figure
9) Such a correlation need not be, however, and an ideal shoe may,
in most situations, have a highly conductive sole and a very modest
resistance from body to ground. There is no implication intended
that vertical resistance is unimportant, simply that it may not
play a major role in that static whose origin is the floor/shoe
interface

Figure 13: Audit Data
Figure 13 is a depiction of the
effects of foot grounding systems and mode of usage in two different
carpeted assembly and test areas of a medical electronics manufacturing
plant. The test subject was the ESD supervisor.
The legends on the graph are defined
as:
-
"none" =
no heel grounders -street shoes
-
"HG Norm" =
heel grounders on both feet and walking in a normal manner
-
"HG Care" =
heel grounders on both shoes and walking with extreme care to
perform heel-toe movements.
-
"Toe/Heel" =
each shoe had a combination heel and toe grounder attached ,
normal walking manner
Because the measured resistances were
so far out of specification, heel grounders were required on the
assumption that they would be more effective than ESD shoes. The
supervisor reluctantly removed his grounders and was clocked at
1200 peak volts walking normally in the test bench area. With heel
grounders his potential dropped to 250 in one installation and 450
in the other, these being the peaks when both heels left the floor,
as they did with nearly every step. When care was taken not to allow
simultaneous contact loss with both grounders the values were 40
and 170 volts respectively. When he used a sole grounder, which
is essentially a combination of heel and toe grounders, the peak
voltage in both cases dropped below 30 volts. A sole grounder creates
what is really a conductive sole shoe with no opportunity for the
basic, high generating sole to take part and no possibility of a
momentary loss of contact. Controlling the source, the floor/shoe
generator, is a major factor. Figure 14 graphs additional data from
the same installation with additional footwear and operators.

Figure 14a:

Figure 14b:

Figure 14c:
From these data it can be seen that
either of two pairs of shoes produced very little static. There
is little choice electrically among the sole grounder and the two
more conductive shoes. It is apparent that the more conductive soles
were able to exploit the "local" surface conductivity
of the carpet, but that’s another story.
How hazardous are the peak values
associated with foot grounders? As before, we don’t really know.
It’s a judgment call again, but what does a performance standard
requiring personnel voltages to be maintained below 100 volts mean
in a case like this, and how should it be audited?
While we have dwelled on the control
of foot generated static and have shown that body-to-ground resistance
plays only a minor role, other potential sources must not be neglected.
If proper protocol is not followed, seating/clothing static, for
example, can be considerable and calls for a body grounding mechanism
whether ground strap or shoe/floor. If "good" clothing
and "good" seating are used, the grounding needs are small,
even as with a good shoe/floor combination. Figure 15 shows the
grounding requirement for a very lively smock/seat combination.

Figure 15: Control of Clothing/Seating
Static
The voltage on an individual wearing
high resistance clothing was monitored as he quickly arose from
a high resistance chair, keeping insulative shoes immobile on the
floor, and with varying wrist grounder resistances. Peak voltages
were of very short duration for resistance values below 109
W and essentially disappeared for values below 107 W.
Does this mean that a value of less than 107 W is necessary
to protect against peak voltages? Again, probably not, but the offending
furniture and clothing should be addressed.
Conclusions and Recommendations
Today too many people still consider
floors and footwear independently. Floors and Footwear must
be chosen as a system. A good floor will not cover up bad footwear,
nor will good footwear cover up a bad floor.
Present 5 lb. weight electrodes
are not adequate for judging floor performance. Floor resistance
should be measured using the heel electrode methodology at 100
Volts. This method is more representative and reproducible. This
due to the weight of the electrodes being more representative
of those experienced in normal applications and due to the ease
of use especially for large floor areas.
Present definitions and therefore
test methodology for determining performance of footwear is inadequate.
As a result shoe construction is often far from optimum. The shoe
has been considered a monolithic device when in fact it must perform
two nearly independent functions. First it should provide an electrical
connection between the person and the floor without compromising
electrical safety for the person. Second its shoe/floor interface
must provide for a rapid recombination of generated charge. The
following shoe construction is recommended for optimum performance:
Outer sole surface resistance should
ideally be less than 107 W . The more conductive
the outer sole the better as more recombination of charge occurs
(and thus lower personnel voltages). The only limiting factor
should be the floor marking concerns of highly carbon loaded sole
materials or other physical considerations.
The midsole construction of the
shoe should be insulative enough to obviate any electrical safety
concerns.
Users find it confusing that the
resistance limits for defining conductive floors are very different
from those for defining conductive packaging. Terms like "dissipative"
and "conductive" are not necessary nor helpful. A continuous
scale of resistance should used..
Present methodology for determining
flooring resistance is inadequate.
- Floor resistance to ground should be less
than 108 W as measured with the heel electrodes
at 100 Volts for optimum performance.
- The construction of the floor and the grounding
system should be insulative enough to obviate any electrical
safety concerns
All audits must include an evaluation
of static potential on the person appearing from all causes as
well as an audit of contributing factors, such as shoe and floor
resistances.
Tips for ESD Flooring Installations
Because the electrical properties
of floors depend so greatly on installation, the following comments
are made:
It is likely that most ESD coordinators
or consultants only get one or two opportunities to influence
the choice of ESD Flooring and its installation process during
their tenure. This is such an expensive, critical job that some
key considerations must be addressed.
1.ESD Coordinators must be proactive.
It is too late to specify the floor after it is installed. This
means working with Corporate Real Estate in addition to local facilities
personnel. Being proactive is necessary to avoid ESD considerations
being just an afterthought. It is much easier to get the job done
right when involved from the very beginning. Remember: you will
have to live with the floor and its ESD Audit performance for several
years.
2.Understand the floor preparation processes,
the installation processes, and cleaning/maintenance processes.
These are critical to having a successful project. Make sure the
floor has a moisture emission test performed prior to the selection
of the ESD floor. Follow the manufacturer's instructions carefully
for floor preparation, installation and electrically grounding.
3.Use only qualified installers. One of
the most important aspects of the installation is the adhesive
in regards to spreading, curing and coverage.
4.Maintain records of measured resistance.
No traffic should be allowed on vinyl or epoxy floors before
curing is complete.
5.After 48 hours evaluate the
installed floor. Make a sketch of the area ahead of time showing
the measurement points.
- Klein, William G., "Floor Generated Static-A
Resistance Limited Phenomenon," Compliance Engineering,
Fall 1991.
- Fowler, Stephen L. and William G. Klein, "Static
Phenomena and Test Methods for Static Controlled Floors,"
EOS/ESD Symposium Proceedings, 1992.
- Klein, William G., "Performance Oriented
Design and Test Procedures for Static Control Footwear,"
EOS/ESD Symposium Proceedings, 1993.
- Freeman, P.S. and R.Y. Moss, " Sources
of Error in Resistance Measurements on Conductive Flooring,"
EOS/ESD Symposium Proceedings, 1991.
- Hewlett Packard Document A-5951-1589-1, "Workmanship
Specifications for ESD Control," Revision F, Appendices
M and O.
- ESD Association Standard 7.1, "Floor Resistance-Resistive
Characterization of Materials".
- Janszen, Arthur, Unpublished Work, Brunswick
Corporation, 1967.
- ESD Association Standard 9.1, "Footwear-Resistive
Characterization".
- ANSI Z-41, Safety Footwear.
- NFPA 99, Health Care Facilities.
- ASTM F-150, Electrical Resistance of Conductive
Resilient Flooring.
12. AATCC 134, Static Propensity of Carpets.
|